FeaturesThe Liquid Level Controller is a control unit (relay), with the following features:
Features
Optimization The Liquid Level Controller features a complete integrated User Interface with a 32 character dot-matrix display. The User Interface is a tool which is used to display or optimize various settings of the Liquid Level Controller. The detailed explanation of this User Interface is included in the Liquid Level Controller's user manual.
Robust Enclosure The Liquid Level Controller comes in a robust, DIN-rail mountable, powder-coated, steel enclosure.
Fault Output Relay The Liquid Level Controller is fitted with a fault output relay, which may be used to power a 250V load (up to 6A), for example a siren, an emergency light, etc. Available contacts: Common, N/O (Normally Opened) and N/C (Normally Closed).
Pump Control Relays Two pump control relays with Common and N/O (Normally Opened) contacts, which can drive 250V loads (up to 6A) for driving one or two small sewage pumps or contactors.
Pressure Transducer The Liquid Level Controller's Pressure Transducer is currently only available in a 1bar differential pressure option. This transducer can be used to measure a water depth between 0.5 and 10 meters. The transducer also includes a temperature sensor to give the added benefit of viewing the temperature of the liquid with the Liquid Level Controller. The Pressure Transducer comes with a standard 6m cable (customizable up to 50m).
|
| CONTROLLER TECHNICAL SPECIFICATIONS | |
| Supply Voltage: | 190 - 250 VAC |
| Max Relay Contact Voltage: | 250 VAC |
| Max Relay Contact Current: | 6 A |
| Consumption: | 3 VA |
| Controller Temp Range: | -15°C to +70°C |
| Weight: | ± 1kg |
| Dimensions: | 125 x 120 x 80 mm (LxHxW) |
| SENSOR TECHNICAL SPECIFICATIONS | |
| Supply Voltage: | 14 - 25 VDC |
| Pressure Range: | 0.5 meters to 10 meters water (0.05 - 1.0 bar) |
| Temperature Range: | -15°C to +65°C |
| Compatible Fluids: | Any fluid NOT corrosive to PVC, Polly-utherane and Sillicone. |
| Standard Cable Length: | 6 meters |
| Maximum Cable Length: | 50 meters |
| Weight (with cable): | +-1kg |
| Dimensions (sensor only): | Length = 180mm, Diameter = 46mm |
![]()
Instruction manual
|
![]()
Quick links: [Request a quotation or place and order]
![]()
Last modified: 2011-02-28 |