Motorscope S2LC (upto 37kW)

R7,684.00

The Motorscope S2LC is a compact dual motor protection unit with an integrated level controller and more.

Category:

Description

The Motorscope S2LC is a dual pump protection unit with:

  • Flip-flop
  • Level control (4 inputs)
  • 2x Termistor inputs (clickson)
  • 2x Humidi sensor inputs.
  • 2x Supra Motorscope Units
  • Alarm Output

Additional information

Protection

Over-load (e.g. pump jammed)
Under-load (e.g. run-dry)
Over-Voltage
Under-Voltage
Phase Failure (e.g. a wire is cut)
Phase sequence changes (e.g. after a power failure, the phases are swapped)
Phase Imbalance (e.g. one of the phases carries more load than the other two)
Not against lightning

Features

LEVEL CONTROL: Filling or Emptying, Float Switches or Probes, Manual or Auto.

TWO ALARM RELAYS: The two Supras share an alarm output for: Over Current, Over Power, Minimum Phase Angle, No Current and Uncalibrated. Shared level and pump alarm output for: Either high or Low level, Oil sump water detection, Controller Error.

RECOVERY TIMERS: Each Supra has its own Recover Timer to allow the sump to fill up before a restart attempt is made (after a run-dry condition). These timers are manually adjustable from 4 minutes to 16 hours.

REAL-TIME CLOCK: Each Supra has a real-time clock. This allows each unit to store the date and time (year, month, day, hour, minute) of each one of the last 43 trips.

Technical Specifications

MOTOR VOLTAGE (3PH): L1→L2→L3=415VAC
MOTOR VOLTAGE (1PH): L1→L2=230VAC
POWER RANGE: 1→37kW
FREQUENCY RANGE: 40→70 Hz
CONSUMPTION: 14 VA
3 TOP RELAYS: 400V:16A
1 BOTTOM RELAY: 230V:8A
COS PHI RANGE: 0→1 Inductive
TEMP RANGE: -15→+70°C
WEIGHT: 2kg
DIMENSIONS: 248 x 162 x 126 mm
MAX CABLE LENGTH OF FLOAT SWITCH: 300 m

External CT Shunt Resistor Values (For A 2.5VA, 250:1 CT)

1-12 Amp → 32Ω → CT Ration 1
8-24 Amp → 16Ω → CT Ration 2
20-48 Amp → 8Ω → CT Ration 4
40-96 Amp → 4Ω → CT Ration 8
70-170 Amp → 2Ω → CT Ration16

Built-in User Interface Options

The S2LC has a dedicated serial port for each Supra to which the following Built-in User interface options could be connected:

– A single Mobi Board (Bluetooth Interface to App) which can manually be moved from one Supra’s serial port to the other.

– Two Mobi Boards (one for each Supra)

– A single Built-in Optimizer which can manually be moved from the one Supra’s serial port to the other Unfortunately the Built-in optimizers are too big to allow two of them to fit into each-other on the S2LC therefore no dual Built-In Optimizer option is available.

Reviews

There are no reviews yet.

Be the first to review “Motorscope S2LC (upto 37kW)”